Skip to main content
Loading…
This section is included in your selections.

A. The following are modifications or amendments to the International Fire Code, 2021 Edition, as adopted in RMC 15.06.011, and shall correspond to the context of said International Fire Code as if set out at length in their respective sections in lieu of or in addition to published sections or subsections. Where an amendment or modification replaces a published section or subsection, the published section or subsection shall be deemed void and deleted.

1. Amend 102.5 to read as follows:

102.5 Application of residential code.

Where structures are designed and constructed in accordance with the International Residential Code, including, without exception, all new licensed adult family homes in existing structures, the provisions of this code shall apply as follows:

1. Construction and design provisions of this code pertaining to the exterior of the structure shall apply including, but not limited to, premises identification, fire apparatus access and water supplies. Where interior or exterior systems or devices are installed, construction permits required by Section 105.6 apply.

2. Administrative, operational and maintenance provisions of this code and requirements of R.M.C. 15.06.016 shall apply.

2. Amend Section 102.7 to read as follows:

102.7 Referenced codes and standards.

The codes and standards referenced in this code shall be the Redmond Fire Department Standards and those that are listed in Chapter 80. Such codes and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections 102.7.1; 102.7.2, and 102.7.3. Redmond Fire Department Standards shall constitute the primary reference document and guideline. Where differences occur between the provisions of this code and the referenced standards, the provisions of this code shall apply.

3. Add Section 102.7.3 as follows:

102.7.3 Supplemental rules and regulations.

The fire code official is authorized to render interpretations of this code and to make and enforce rules and supplemental regulations in order to carry out the application and intent of its provisions. Such interpretations, rules, and regulations shall be known as the Redmond Fire Department Standards and shall be in conformance with the intent and purpose of this code and shall be available to the public during normal business hours.

4. Add Section 104.6.5 as follows:

104.6.5 Documentation of required maintenance

When required by the fire code official documentation of maintenance to fire safety features or systems required by this code shall be submitted to the fire code official in an approved method, manner, and form. Fees associated with such documentation shall be in accordance with the adopted fee schedule.

5. Amend Section 104.12.2 to read as follows:

104.12.2 Obstructing operations.

Persons shall not obstruct the operations of the fire department in connection with extinguishment, control, or investigation of any fire or actions relative to other emergencies or disobey any lawful command of the fire chief or officer of the fire department in charge of the emergency, or any part thereof, or any lawful order of a police officer assisting the fire department.

6. Add Section 104.13 as follows:

104.13 Assistance from other agencies.

Police and other enforcement agencies shall have authority to render necessary assistance in the enforcement of this code as requested by the fire code official.

7. Amend Section 105.2.3 to read as follows:

105.2.3 Time limitation of application.

An application for a permit for any proposed work or operation shall be deemed to have been abandoned 365 days after the date of filing, unless such application has been diligently prosecuted or a permit shall have been issued; except that the fire code official is authorized to grant one or more extensions of time for additional periods not exceeding 365 days each. The extension shall be requested in writing and justifiable cause demonstrated.

8. Amend Section 105.3.1 to read as follows:

105.3.1 Expiration.

An operational permit shall remain in effect until reissued, renewed or revoked, or for such a period of time as specified in the permit. Construction permits shall automatically become invalid unless the work authorized by such permit is commenced within 365 days after its issuance, or if the work authorized by such permit is suspended or abandoned for a period of 365 days after the time the work is commenced. Before such work recommences, a permit shall be first obtained and the fee to recommence work, if any, shall be one-half the amount required for a new permit for such work; provided, that changes have not been made and will not be made in the original construction documents for such work, and provided further that such suspension or abandonment has not exceeded one year. Permits are not transferable and any change in occupancy, operation, tenancy or ownership shall require that a new permit be issued.

9. Amend Section 105.3.2 to read as follows:

105.3.2 Extensions.

A permittee holding an unexpired permit shall have the right to apply for an extension of the time within which the permittee will commence work under that permit where work is unable to be commenced within the time required by this section for good and satisfactory reasons. The fire code official is authorized to grant, in writing, one or more extensions of the time period of a permit for periods of not more than 365 days each. Such extensions shall be requested by the permit holder in writing and justifiable cause demonstrated.

10. Amend Section 105.5.25 to read as follows:

105.5.25 Hot-work operations.

An operational permit is required for hot-work including, but not limited to:

1. Public exhibitions and demonstrations where hot-work is conducted.

2. Use of portable hot-work equipment inside a structure.

Exception 1: Work that is conducted under a construction permit.

Exception 2: Less than 16 ounces in self-contained, handheld devices that do not allow gas flow or flame when the trigger is released.

3. Fixed-site hot-work equipment such as welding booths.

4. Hot-work conducted within a wildfire risk area.

5. Application of roof coverings with the use of an open-flame device.

6. When approved, the fire code official shall issue a permit to carry out a hot work program. This program allows approved personnel to regulate their facility’s hot work operations. The approved personnel shall be trained in the fire safety aspects denoted in this chapter and shall be responsible for issuing permits requiring compliance with the requirements found in Chapter 35. These permits shall be issued only to their employees or hot-work operations under their supervision.

11. Amend Section 105.5.29 to read as follows:

105.5.29 LP-gas.

An operational permit is required for:

1. Storage and use of LP-gas.

Exception 1: A permit is not required for individual containers with a 500-gallon (1893 L) water capacity or less or multiple container systems having an aggregate quantity not exceeding 500 gallons (1893 L) serving occupancies in Group R-3.

Exception 2: In other than R-3 occupancies, a permit is not required in noncommercial outdoor use of propane barbecue grills.

2. Operation of cargo tankers that transport LP-gas.

12. Amend Section 105.5.32 to read as follows:

105.5.32 Mobile food preparation vehicles.

A permit is required for food preparation vehicles equipped with appliances that produce smoke or grease-laden vapors or utilize LP-gas or CNG systems. A permit issued from a public fire agency approved by the fire code official may be accepted in lieu of a Redmond Fire Department operational permit.

13. Amend Section 105.5.45 to read as follows:

105.5.45 Repair garages.

An operational permit is required for the operation of repair garages.

14. Add Section 105.5.53 to read as follows:

105.5.53 Fire alarm systems.

A fire alarm operational permit is required to operate all fire alarm systems required by Chapter 9 or RMC 15.06.015.

Point of Information: This requirement will apply to all systems effective January 1, 2021.

15. Amend Section 105.6.3 to read as follows:

105.6.3 Cryogenic fluids.

A construction permit is required for installation of or alteration to stationary cryogenic fluid storage systems where the system capacity exceeds the amounts listed in Table 105.5.11. Maintenance performed in accordance with this code is not considered an alteration and does not require a construction permit.

16. Amend Section 105.6.19 as follows:

105.6.19 Smoke control or smoke exhaust systems.

Construction permits are required for installation of or alteration to smoke control or smoke exhaust systems regulated by Chapter 9. Maintenance performed in accordance with this code is not considered to be an alteration and does not require a permit.

17. Add Section 105.6.26 as follows:

105.6.26 HPM facilities.

A construction permit is required to install equipment or facilities that store, handle, or use hazardous production materials.

18. Add Section 105.6.27 as follows:

105.6.27 Refrigeration equipment.

A construction permit is required to install a mechanical refrigeration unit or system regulated by Chapter 6 of the IFC.

19. Add Section 105.6.28 as follows:

105.6.28 Places of assembly.

A construction permit is required for all new place of assembly uses.

20. Amend section 111 as follows:

111.1 Appeals

Whenever the fire code official or designee disapproves an application or refuses to grant a permit applied for, or when it is claimed that the provisions of the code do not apply or that the true intent and meaning of the code has been misconstrued or wrongly interpreted, the applicant may appeal to the Chief of the Fire Department in accordance with the procedures for Type 1 Review, RZC 21.76.060(d). Appeals from the decisions of the Chief to the Hearing Examiner shall be made as prescribed in RZC 21.76.060(d)(4).

111.2 Limitations on authority: Section not adopted.

111.3 Qualifications: Section not adopted.

111.4 Administration: Section not adopted.

21. Add Section 114.8 as follows:

114.8 Fire- or explosion-damaged buildings.

The owner, occupant, or other person having under his control any property or materials on a property damaged by fire or explosion shall, when ordered by the fire chief, immediately secure the property against entry or unauthorized access by the public, by boarding up all openings, fencing, barricading or utilizing other appropriate measures. Within 30 days after written notice to do so has been served, all debris and/or damaged materials shall be removed from the property and proof furnished that contractual arrangements have been made for prompt demolition, replacement, or repair of all fire- or explosion-damaged structures remaining on the property involved in the fire or explosion.

22. Add/amend Section 202 as follows:

1. Amend the definition(s) of “Facility” and “High-Rise Buildings” to read as follows:

FACILITY.

A building or use in a fixed location including exterior storage areas for flammable and combustible substances and hazardous materials, piers, wharves, tank farms, parks, plazas, sport fields, or other public assembly areas and similar uses. This term includes recreational vehicles, mobile home and manufactured housing parks, sales, and storage lots.

HIGH-RISE BUILDINGS:

A building with an occupied floor or occupied roof located more than 75 feet (22,860 mm) above the lowest level of fire department vehicle access.

23. Amend Section 307.1 to read as follows:

307.1 General.

A person shall not kindle or maintain, or authorize to be kindled or maintained, any open burning unless conducted and approved in accordance with Sections 307.1.1 through 307.5, see also Chapter 173-425 WAC.

24. Amend Section 307.4.2 to read as follows:

307.4.2 Recreational fires.

Recreational fires shall not be conducted within 50 feet (15,240 mm) of a structure or combustible material. Conditions that could cause a fire to spread within 50 feet (15,240 mm) of a structure shall be eliminated prior to ignition.

25. Amend Section 307.4.3 to read as follows:

307.4.3 Portable outdoor fireplaces.

Portable outdoor fireplaces shall be used in accordance with the manufacturer’s instructions and shall not be operated within 15 feet (3048 mm) of a structure or combustible material.

26. Add Section 503.1.1.1 to read as follows:

503.1.1.1 Extent of access.

The fire apparatus access roadway shall extend to within 50 feet of at least 25 percent of the perimeter of the building. Where access roadway cannot be provided, the fire code official is authorized to require an approved fire protection system or systems as provided in RMC 15.06.017.

Exception: Detached one- and two-family dwelling units.

27. Add Section 503.1.1.2 to read as follows:

503.1.1.2 Easements.

When directed by the fire code official, emergency vehicle access routes or areas, including emergency vehicle operations areas, turnarounds, overhang areas, firefighter access, emergency egress, or similar, that are not within a public right-of- way shall be maintained in an approved and recorded emergency vehicle access and/or firefighter access easement.

28. Add section 503.1.4 to read as follows:

503.1.4 Emergency Medical Access.

When an elevator is required in a building, access for aid or medic vehicles shall be provided as follows or as approved by the fire code official:

1. Vehicular access shall be provided to a dedicated parking space that is located within 75 feet (22,860 mm) of travel distance to a 4 foot by 7-foot elevator that serves each floor or area of a structure.

2. The path from the parking space to the elevator shall not contain stairs, obstructions, or grade changes that prevent the safe use of a stretcher.

3. When the parking space is provided within a structure or parking garage, the minimum clear height shall be as specified by the fire code official but not less than 10 feet. If this space is provided along a street the minimum length of the parking space shall be not less than 30 feet (9,140 mm).

4. The minimum width and turning radii shall be the same as other required fire access unless approved by the fire code official.

29. Add Section 503.2.7.1 as follows:

503.2.7.1 Maximum grade.

All required access roadways shall be constructed so that the maximum gradient is 10 percent. Where this requirement cannot be met, the fire code official is authorized to require approved safeguards as identified in RMC 15.06.017.

30. Amend Section 503.2.8 to read as follows:

503.2.8 Angles of approach and departure.

The angles of approach and departure for fire apparatus access roads shall be within the limits established by the fire code official based on the fire department’s apparatus. No access roadway or access road approach to a public way shall have an arc higher than 12 inches in less than 20 feet. Where these requirements cannot be provided, the fire code official is authorized to require approved safeguards as identified in RMC 15.06.017.

31. Amend Section 503.4 as follows:

503.4 Obstructions of fire lanes and fire apparatus access roads.

Fire lanes and fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 and 503.2.2 shall be maintained at all times. The fire chief shall have the power and authority to remove or cause to be removed without notice, any vehicle, vessel, or thing parked or placed in violation of Section 503.4 of the International Fire Code. The fire chief may direct a property owner or property manager of a commercial or multifamily development to have such vehicles towed and/or contract with a towing company to have such vehicles towed when necessary to maintain fire access unobstructed. The owner of any item so removed shall be responsible for all towing, storage, and other charges connected therewith.

32. Add Section 505.3 to read as follows:

505.3 Street and road designations.

Street and road designations shall be as determined and assigned by the fire chief.

33. Amend Section 507.5 to read as follows:

507.5 Fire hydrant systems.

Fire hydrant systems along public or private roads shall comply with Sections 507.5.1 through 507.5.6. Hydrant spacing in commercial and multifamily shall be 300 feet (91,440 mm) on-center; hydrant spacing for single-family residences shall be 600 feet (182,880 mm) on center.

34. Amend Section 507.5.1 to read as follows:

507.5.1 Where required.

Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.

Exceptions:

1. For group R-3, Group U and one- and two-family dwellings, the distance requirement shall be 450 feet (137,160 mm).

2. For Group R-3, Group U, and one- and two-family dwellings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3, the distance requirement shall be 600 feet (182,880 mm).

35. Amend Section 507.5.1.1 to read as follows:

507.5.1.1 Hydrant for sprinkler and standpipe systems.

Buildings equipped with a sprinkler or standpipe system installed in accordance with Section 903 or 905 shall have a fire hydrant within 40 feet of the fire department connections.

Exception: The distance shall be permitted to exceed 40 feet where approved by the fire code official.

36. Replace the existing language in Section 510 with the following:

510.1 Emergency responder radio coverage in new buildings.

Approved radio coverage for emergency responders shall be provided within buildings meeting any of the following conditions:

1. High rise buildings.

2. The total building area is 50,000 square feet or more.

3. The total basement area is 10,000 square feet or more; or

4. There are floors used for human occupancy more than 30 feet below the finished floor of the lowest level of exit discharge.

5. Buildings or structures where the fire or police chief determines that in- building radio coverage is critical because of its unique design, location, use or occupancy.

The radio coverage system shall be installed in accordance with Sections 510.4 through 510.5.5 of this code and with the provisions of NFPA 1221 (2019). This section shall not require improvement of the existing public safety communication systems.

Exceptions:

1. Buildings and areas of buildings that have minimum radio coverage signal strength levels of the King County regional 800 MHz radio system within the building in accordance with Section 510.4.1 without the use of a radio coverage system.

2. In facilities where emergency responder radio coverage is required and such systems, components, or equipment required could have a negative impact on the normal operations of that facility, the fire code official shall have the authority to accept an automatically activated emergency responder radio coverage system.

3. One- and two-family dwellings and townhouses.

4. Subject to the approval of the fire code official, buildings other than high- rise buildings, colleges, universities, and buildings primarily occupied by Group E or I occupancies that have completed a mobile emergency responder radio coverage application and submitted payment as outlined in the application.

510.2 Emergency responder radio coverage in existing buildings.

Existing buildings shall be provided with approved radio coverage for emergency responders as required in Chapter 11.

510.3 Permit required.

A construction permit for the installation of or modification to emergency responder radio coverage systems and related equipment is required as specified in Section 105.7.6. Maintenance performed in accordance with this code is not considered a modification and does not require a permit.

510.4 Technical requirements.

Systems, components, and equipment required to provide the emergency responder radio coverage system shall comply with Sections 510.4.1 through 510.4.2.8.

510.4.1 Emergency responder communication enhancement system signal strength.

The building shall be considered to have acceptable emergency responder communications enhancement system coverage when signal strength measurements in 95 percent of all areas on each floor of the building meet the signal strength requirements in Sections 510.4.1.1 through 510.4.1.3.

Exception: Critical areas, such as the fire command center(s), the fire pump room(s), interior exit stairways, exit passageways, elevator lobbies, standpipe cabinets, sprinkler sectional valve locations, and other areas required by the fire code official, shall be provided with 99 percent floor area radio coverage.

510.4.1.1 Minimum signal strength into the building.

The minimum inbound signal strength shall be sufficient to provide usable voice communications throughout the coverage area as specified by the fire code official. The inbound signal level shall be a minimum of -95 dBm in 95% of the coverage area and 99% in critical areas and sufficient to provide not less than a delivered audio quality (DAQ) of 3.0 or an equivalent signal-to-interference-plus-noise ratio (SINR) applicable to the technology for either analog or digital signals.

510.4.1.2 Minimum signal strength out of the building.

The minimum outbound signal strength shall be sufficient to provide usable voice communications throughout the coverage area as specified by the fire code official. The outbound signal level shall be sufficient to provide not less than a DAQ of 3.0 or an equivalent SINR applicable to the technology for either analog or digital signals. A minimum signal strength of -95 dBm shall be received by the King County regional 800 MHz radio system when transmitted from within the building.

510.4.1.3 System performance. Signal strength shall be sufficient to meet the requirements of the applications being utilized by public safety for emergency operations through the coverage area as specified by the radio system manager in Section 510.4.2.2.

510.4.2 System design.

The emergency responder radio coverage system shall be designed in accordance with Sections 510.4.2.1 through 510.4.2.8 and NFPA 1221 (2019).

510.4.2.1 Amplification systems and components.

Buildings and structures that cannot support the required level of radio coverage shall be equipped with systems and components to enhance the public safety radio signals and achieve the required level of radio coverage specified in Sections 510.4.1 through 510.4.1.3. Public safety communications enhancement systems utilizing radio-frequency-emitting devices and cabling shall be allowed by the public safety radio system operator. Prior to installation, all radio frequency (RF)-emitting devices shall have the certification of the radio licensing authority and be suitable for public safety use.

510.4.2.2 Technical criteria.

The public safety radio system operator shall provide the various frequencies required, the location of radio sites, the effective radiated power of radio sites, the maximum propagation delay in microseconds, the applications being used and other supporting technical information necessary for system design upon request by the building owner or owner’s representative.

510.4.2.3 Power supply sources.

Emergency responder radio coverage systems shall be provided with dedicated standby batteries or provided with 2-hour standby batteries and connected to the facility generator power system in accordance with Section 1203. The standby power supply shall be capable of operating the emergency responder radio coverage system at 100-percent system capacity for a duration of not less than 12 hours.

510.4.2.4 Signal booster requirements.

If used, signal boosters shall meet the following requirements:

1. All signal booster components shall be contained in a National Electrical Manufacturer’s Association (NEMA) 4 IP66-type waterproof cabinet or equivalent.

Exception: Listed battery systems that are contained in integrated battery cabinets.

2. Battery systems used for the emergency power source shall be contained in a NEMA 3R or higher-rated cabinet, IP65-type waterproof cabinet or equivalent.

3. Equipment shall have FCC or other radio licensing authority certification and be suitable for public safety use prior to installation.

4. Where a donor antenna exists, isolation shall be maintained between the donor antenna and all inside antennas to not less than 20 dB greater than the system gain under all operating conditions.

5. Bidirectional amplifiers (BDAs) used in emergency responder radio coverage systems shall be fitted with anti-oscillation circuitry and per- channel AGC.

6. The installation of amplification systems or systems that operate on or provide the means to cause interference on any emergency responder radio coverage networks shall be coordinated and approved by the public safety radio system operator.

7. Unless otherwise approved by the public safety radio system operator, only channelized signal boosters shall be permitted.

Exception: Broadband BDAs may be utilized when specifically authorized in writing by the public safety radio system operator.

510.4.2.5 System monitoring.

The emergency responder radio enhancement system shall include automatic supervisory and trouble signals that are monitored by a supervisory service and are annunciated by the fire alarm system in accordance with NFPA 72. The following conditions shall be separately annunciated by the fire alarm system, or, if the status of each of the following conditions is individually displayed on a dedicated panel on the radio enhancement system, a single automatic supervisory signal may be annunciated on the fire alarm system indicating deficiencies of the radio enhancement system:

1. Loss of normal AC power supply.

2. System battery charger(s) failure.

3. Malfunction of the donor antenna(s).

4. Failure of active RF-emitting device(s).

5. Low-battery capacity at 70-percent reduction of operating capacity.

6. Active system component malfunction.

7. Malfunction of the communications link between the fire alarm system and the emergency responder radio enhancement system.

510.4.2.6 Additional frequencies and change of frequencies.

The emergency responder radio coverage system shall be capable of modification or expansion in the event frequency changes are required by the Federal Communications Commission (FCC) or other radio licensing authority or additional frequencies are made available by the FCC or other radio licensing authority.

510.4.2.7 Design documents.

The fire code official shall have the authority to require as-built design documents and specifications for emergency responder communications coverage systems. The documents shall be in a format acceptable to the fire code official.

510.4.2.8 Radio communication antenna density.

Systems shall be engineered to minimize the near-far effect. Radio enhancement system designs shall include sufficient antenna density to address reduced gain conditions.

Exceptions:

1. Class A narrow band signal booster devices with independent AGC/ALC circuits per channel.

2. Systems where all portable devices within the same band use active power control.

510.5 Installation requirements.

The installation of the public safety radio coverage system shall be in accordance with NFPA 1221 and Sections 510.5.1 through 510.5.7.

510.5.1 Approval prior to installation.

Amplification systems capable of operating on frequencies licensed to any public safety agency by the FCC or other radio licensing authority shall not be installed without prior coordination and approval of the public safety radio system operator.

510.5.2 Minimum qualifications of personnel.

The minimum qualifications of the system designer and lead installation personnel shall include both of the following:

1. A valid FCC-issued general radio telephone operators license.

2. Certification of in-building system training issued by an approved organization or approved school, or a certificate issued by the manufacturer of the equipment being installed.

510.5.3 Acceptance test procedure.

Where an emergency responder radio coverage system is required, and upon completion of installation, the building owner shall have the radio system tested to verify that two-way coverage on each floor of the building is in accordance with Section 510.4.1. The test procedure shall be conducted as follows:

1. Each floor of the building shall be divided into a grid of 20 approximately equal test areas with a maximum test area size of 6,400 square feet. Where the floor area exceeds 128,000 square feet, the floor shall be divided into as many approximately equal test areas as needed such that no test area exceeds the maximum square footage allowed for a test area.

2. Coverage testing of signal strength shall be conducted using a calibrated spectrum analyzer for each of the test grids. A diagram of this testing shall be created for each floor where coverage is provided, indicating the testing grid used for the test in Section 510.5.3(1) and including signal strengths and frequencies for each test area. Indicate all critical areas.

3. Functional talk-back testing shall be conducted using two calibrated portable radios of the latest brand and model used by the agency’s radio communications system or other equipment approved by the fire code official. Testing shall use digital audible quality (DAQ) metrics, where a passing result is a DAQ of 3 or higher. Communications between handsets shall be tested and recorded in the grid square diagram required by section 510.5.3(2): each grid square on each floor; between each critical area and a radio outside the building; between each critical area and the fire command center or fire alarm control panel; between each landing in each stairwell and the fire command center or fire alarm control panel.

4. Failure of more than 5% of the test areas on any floor shall result in failure of the test.

Exception: Critical areas shall be provided with 99 percent floor area coverage.

5. In the event that two of the test areas fail the test, in order to be more statistically accurate, the floor shall be permitted to be divided into 40 equal test areas. Failure of not more than two nonadjacent test areas shall not result in failure of the test. If the system fails the 40-area test, the system shall be altered to meet the 95-percent coverage requirement.

6. A test location approximately in the center of each test area shall be selected for the test, with the radio enabled to verify two-way communications to and from the outside of the building through the public agency’s radio communications system. Once the test location has been selected, that location shall represent the entire test area. Failure in the selected test location shall be considered to be a failure of that test area. Additional test locations shall not be permitted.

7. The gain values of all amplifiers shall be measured, and the test measurement results shall be kept on file with the building owner so that the measurements can be verified during annual tests. In the event that the measurement results become lost, the building owner shall be required to rerun the acceptance test to reestablish the gain values.

8. As part of the installation, a spectrum analyzer or other suitable test equipment shall be utilized to ensure spurious oscillations are not being generated by the subject signal booster. This test shall be conducted at the time of installation and at subsequent annual inspections.

9. Systems incorporating Class B signal booster devices or Class B broadband fiber remote devices shall be tested using two portable radios simultaneously conducting subjective voice quality checks. One portable radio shall be positioned not greater than 10 feet (3048 mm) from the indoor antenna. The second portable radio shall be positioned at a distance that represents the farthest distance from any indoor antenna. With both portable radios simultaneously keyed up on different frequencies within the same band, subjective audio testing shall be conducted and comply with DAQ levels as specified in Sections 510.4.1.1 and 510.4.1.2.

10. Documentation maintained on premises.

At the conclusion of the testing and prior to issuance of the building certificate of occupancy, the building owner or owner’s representative shall place a copy of the following records in the DAS enclosure or the building engineer’s office. The records shall be available to the fire code official and maintained by the building owner for the life of the system:

a. A certification letter stating that the emergency responder radio coverage system has been installed and tested in accordance with this code and that the system is complete and fully functional.

b. The grid square diagram created as part of testing in Sections 510.5.3(2) and 510.5.3(3).

c. Data sheets and/or manufacturer specifications for the emergency responder radio coverage system equipment, backup battery, and charging system (if utilized).

d. A diagram showing device locations and wiring schematic.

e. A copy of the electrical permit.

11. Acceptance test reporting to fire code official.

At the conclusion of the testing, and prior to issuance of the building certificate of occupancy, the building owner or owner’s representative shall submit to the fire code official a report of the acceptance test in an approved manner.

510.5.4 FCC compliance.

The emergency responder radio coverage system installation and components shall comply with all applicable federal regulations including, but not limited to, FCC 47 CFR Part 90.219.

510.5.5 Mounting of the donor antenna(s).

To maintain proper alignment with the system designed donor site, donor antennas shall be permanently affixed on the highest possible position on the building or where approved by the fire code official. A clearly visible sign shall be placed near the antenna stating, “movement or repositioning of this antenna is prohibited without approval from the fire code official.” The antenna installation shall be in accordance with the applicable requirements in the International Building Code for weather protection of the building envelope.

510.5.6 Wiring.

The backbone, antenna distribution, radiating, or any fiber-optic cables shall be rated as plenum cables. The backbone cables shall be connected to the antenna distribution, radiating, or copper cables using hybrid coupler devices of a value determined by the overall design. Backbone cables shall be routed through an enclosure that matches the building’s required fire-resistance rating for shafts or interior exit stairways. The connection between the backbone cable and the antenna cables shall be made within an enclosure that matches the building’s fire- resistance rating for shafts or interior exit stairways, and passage of the antenna distribution cable in and out of the enclosure shall be protected as a penetration per the International Building Code.

510.5.7 Identification signs.

Emergency responder radio coverage systems shall be identified by an approved sign located on or near the fire alarm control panel or other approved location stating “This building is equipped with an emergency responder radio coverage system. Control equipment located in room”. A sign stating “Emergency Responder Radio Coverage System Equipment” shall be placed on or adjacent to the door of the room containing the main system components.

510.6 Maintenance.

The emergency responder radio coverage system shall be maintained operational at all times in accordance with Sections 510.6.1 through 510.6.7.

510.6.1 Testing and proof of compliance.

The owner of the building or owner’s authorized agent shall have the emergency responder radio coverage system inspected and tested annually or where structural changes occur including additions or remodels that could materially change the original field performance tests. Testing shall consist of the following items:

1. In-building coverage test as required by the fire code official as described in Section 510.5.3 “Acceptance test procedure” or 510.6.1.1 “Alternative in- building coverage test”.

Exception: Group R Occupancy annual testing is not required within dwelling units.

2. Signal boosters shall be tested to verify that the gain/output level is the same as it was upon initial installation and acceptance or set to optimize the performance of the system.

3. Backup batteries and power supplies shall be tested under load of a period of 1 hour to verify that they will properly operate during an actual power outage. If within the 1-hour test period the battery exhibits symptoms of failure, the test shall be extended for additional 1-hour periods until the integrity of the battery can be determined.

4. If a fire alarm system is present in the building, a test shall be conducted to verify that the fire alarm system is properly supervising the emergency responder communication system as required in Section 510.4.2.5. The test is performed by simulating alarms to the fire alarm control panel. The certifications in Section 510.5.2 are sufficient for the personnel performing this testing.

5. Other active components shall be checked to verify operation within the manufacturer’s specifications.

6. At the conclusion of the testing, a report, which shall verify compliance with Section 510.6.1, shall be submitted to the fire code official in an approved manner.

7. At the conclusion of testing, a record of the inspection and maintenance along with an updated grid diagram of each floor showing tested strengths in each grid square and each critical area shall be added to the documentation maintained on the premises in accordance with Section 510.5.3.

510.6.1.1 Alternative in-building coverage test.

When the comprehensive test documentation required by Section 510.5.3 is available or the most recent full five-year test results are available if the system is older than six years, the in-building coverage test required by the fire code official in Section 510.6.1(1), may be conducted as follows:

1. Functional talk-back testing shall be conducted using two calibrated portable radios of the latest brand and model used by the agency’s radio communications system or other equipment approved by the fire code official. Testing shall use digital audible quality (DAQ) metrics, where a passing result is a DAQ of 3 or higher. Communications between handsets in the following locations shall be tested: between the fire command center or fire alarm control panel and a location outside the building; between the fire alarm control panel and each landing in each stairwell.

2. Coverage testing of signal strength shall be conducted using a calibrated spectrum analyzer for:

a. Three grid areas per floor. The three grid areas to be tested on each floor are the three grid areas with poorest performance in the acceptance test or the most recent annual test, whichever is more recent; and

b. Each of the critical areas identified in acceptance test documentation required by Section 510.5.3 or as modified by the fire code official, and

c. One grid square per serving antenna.

3. The test area boundaries shall not deviate from the areas established at the time of the acceptance test or as modified by the fire code official. The building shall be considered to have acceptable emergency responder radio coverage when the required signal strength requirements in 510.4.1.1 and 510.4.1.2 are located in 95 percent of all areas on each floor of the building and 99 percent in critical areas, and any nonfunctional serving antenna are repaired to function within normal ranges. If the documentation of the acceptance test or most recent previous annual test results are not available or acceptable to the fire code official, the radio coverage verification testing described in 510.5.3 shall be conducted.

510.6.2 Additional frequencies.

The building owner shall modify or expand the emergency responder radio coverage system at his or her expense in the event frequency changes are required by the FCC or other radio licensing authority or additional frequencies are made available by the FCC public safety radio system operator or FCC license holder. Prior approval of a public safety radio coverage system on previous frequencies does not exempt this section.

510.6.3 Nonpublic safety system.

Where other nonpublic safety amplification systems installed in buildings reduce the performance or cause interference with the emergency responder communications coverage system, the nonpublic safety amplification system shall be corrected or removed.

510.6.4 Field testing.

Agency personnel shall have the right to enter onto the property at any reasonable time to conduct field testing to verify the required level of radio coverage or to disable a system that due to malfunction or poor maintenance has the potential to impact the emergency responder radio system in the region.

37. Amend Section 605.4 to read as follows:

605.4 Fuel oil storage systems.

Fuel oil storage systems for building heating systems shall be installed and maintained in accordance with this code. Tanks and fuel oil piping systems shall be installed in accordance with chapter 13 of the International Mechanical Code.

Secondary containment shall be provided for all new installations of storage tanks and associated piping.

Exception: Piping that is integral to the fuel-fired appliance.

38. Amend Section 901.4.1 to read as follows:

901.4.1 Required fire protection systems.

Fire protection and life safety systems required by this code or the International Building Code shall be installed, repaired, operated, tested, and maintained in accordance with this code. A fire protection or life safety system for which a design option, exception, or reduction to the provisions of this code or the International Building Code has been granted shall be considered a required system. The Redmond Fire Department Standards applicable to the particular system shall constitute the primary reference document.

39. Amend Section 901.7 to read as follows:

901.7 Systems out of service.

Where a fire protection system is out of service, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shutdown until the fire protection system has been returned to service.

Where utilized, fire watches shall be provided with at least one approved means for notification of the fire department and their only duty shall be to perform constant patrols of the protected premises and keep watch for fires.

Exception: Facilities with an approved notification and impairment management program. The notification and impairment program for water-based fire protection systems shall comply with NFPA 25.

40. Add Section 901.11 to read as follows:

901.11 Problematic fire protection systems:

In the event of repeated system malfunctions or maintenance related activations, the fire code official may declare the system to be a problematic system and is authorized to direct corrective action to be taken. The fire code official is authorized to have the fire protection system taken out of service. The procedures found in Section 901.7 “Systems out of service” shall be followed.

41. Amend Section 903.2 to read as follows:

903.2 Where required.

Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Redmond Municipal Code Section 15.06.016 and IFC Sections 903.2.1 through 903.2.12.

42. Add Section 903.3.9 as follows:

903.3.9 Fire sprinkler and standpipe main/express drains.

Fire sprinkler and standpipe main/express drains shall be positioned to drain to the sanitary sewer. Additionally, maintenance or testing discharges from fire pumps shall be treated in order to comply with the National Pollution Discharge Elimination System (NPDES) requirements.

Exception: This requirement does not apply to systems installed in one- and two-family dwellings and townhomes.

43. Amend Section 903.4.2 to read as follows:

903.4.2 Alarms.

Approved audible and visible alarm notification appliances shall be provided for every automatic sprinkler system in accordance with Section 907 and throughout areas designated by the fire code official. Sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, activation of the automatic sprinkler system shall activate the building fire alarm system.

Exception: With approval of the fire code official, audible and visible alarm notification appliances may be omitted for approved residential sprinkler systems in 1- or 2-dwelling units if not otherwise specifically required.

44. Amend Section 903.4.3 to read as follows:

903.4.3 Floor control valves.

Approved supervised indicating control valves shall be provided at the point of connection to the riser on each floor. The floor control valves shall be located within interior exit stairways and within 6 feet of floors or landings unless chains or other readily approved devices are readily available.

Exceptions:

1. In buildings without interior exit stairways, the location of the floor control valves shall be determined by the fire code official.

2. Approved domestically supplied local systems with 10 heads or less.

3. Approved residential sprinkler systems for 1 or 2 dwelling units if not otherwise specifically required.

45. Amend Section 905.3.1 as follows:

905.3.1 Height.

Class I standpipe systems shall be installed throughout buildings where any of the following conditions exist:

1. Three or more stories are above or below the lowest level of the fire department vehicle access.

2. Where the floor level of the highest story is located more than 30 feet (9,144 mm) above the lowest level of the fire department vehicle access.

3. Where the floor level of the lowest story is located more than 30 feet (9,144 mm) below the highest level of fire department vehicle access.

4. Basements greater than 20,000 square feet.

5. Multiple levels of below grade parking.

Exception: In determining the lowest level of fire department vehicle access, it shall not be required to consider:

1. Recessed loading docks for four vehicles or less, and

2. Conditions where topography makes access from the fire department vehicle to the building impractical or impossible.

46. Amend section 905.3.8 as follows:

905.3.8 Landscaped roofs and courtyards.

Buildings or structures that have landscaped roofs or courtyards and that are equipped with a standpipe system shall have the standpipe system extended so that all portions of the roof level or courtyard on which the landscaped roof or courtyard is located is reachable from a hose connection by a 30-foot hose stream from a nozzle attached to 150 feet of hose.

47. Add Section 905.3.9 to read as follows:

905.3.9 High-rise building standpipes.

High-rise standpipe risers shall be combination standpipe/sprinkler risers using a minimum pipe size of 6 inches. One 2 1/2-inch hose connection shall be provided on every intermediate floor level landing in every required stairway and elsewhere as required by NFPA 14.

Where, and only where, static or residual water pressures at any hose outlet exceeds 175 psi (1207 kPa), approved pressure regulating devices (PRV) shall be installed to limit the pressure to a range between 125 and 175 psi at not less than 300 gpm.

The pressure on the inlet side of the pressure-regulating device shall not exceed the rated working pressure of the device. An additional nonregulated hose connection located directly below the PRV or an equally sized bypass around the PRV with a normally closed control valve shall be provided at each reduced pressure connection. Each nonregulated hose connection shall be labeled “High Pressure-No PRV”. Each sign shall have 1/2-inch white letters on a red background.

48. Add Section 905.3.10 as follows:

905.3.10 Vertical standpipes served by fire pumps in high-rise buildings.

Where vertical standpipes are served by fire pumps, a check valve shall be installed at the base of each vertical standpipe.

49. Amend Section 907.1 as follows:

907.1 General

Redmond Municipal Code 15.06.015 and this section covers the application, installation, performance, and maintenance of fire alarm systems and their components in new and existing buildings and structures. The requirements of Section 907.2 are applicable to new buildings and structures. The requirements of 907.9 are applicable to existing buildings and structures. Redmond Fire Department Standard 9.00, Automatic Alarm Systems, applies to all required systems.

50. Amend Section 907.2 to read as follows:

907.2 Where required – New buildings and structures.

An approved fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures where there is a required sprinkler system, except one- and two-family dwellings as defined in the International Residential Code and in accordance with Sections 907.2.1 through 907.23, and provide occupant notification in accordance with Section 907.5 unless other requirements are provided by another section of this code.

A minimum of one manual fire alarm box shall be provided in an approved location to initiate a fire alarm signal to fire alarm systems employing automatic fire detectors or water-flow detection devices. Where other sections of this code allow elimination of fire alarm boxes due to sprinklers, a single fire alarm box shall be installed.

Exception: The manual fire alarm box is not required for fire alarm systems dedicated to elevator recall control and supervisory service.

51. Amend Section 1011.12.2 as follows:

1011.12.2 Roof access.

Where a stairway is provided to a roof, access to the roof shall be provided through a penthouse complying with Section 1511.2 of the International Building Code.

Exception: In buildings without an occupied roof, access to the roof shall be permitted to be a roof hatch or trap door not less than 16 square feet in area and having a minimum dimension of 3 feet.

52. Amend Section 1103.2 as follows:

1103.2 Emergency responder radio system coverage in existing buildings.

Buildings constructed prior to the implementation of this code shall not be required to comply with the emergency responder coverage provisions except as follows:

1. Whenever an existing wired communication system cannot be repaired or is being replaced.

2. Buildings identified in Section 510.1 undergoing substantial alteration as determined by the fire code official.

3. When buildings, classes of buildings or specific occupancies do not have minimum radio coverage signal strength as identified in Section 510.4.1 and the fire or police chief determines that lack of minimum signal strength poses an undue risk to emergency responders that cannot be reasonably mitigated by other means.

Exception: Where it is determined by the fire code official that the radio coverage system is not needed.

53. Amend Section 1103.8.1 to read as follows:

1103.8.1 Where required.

Existing group I-1 and R occupancies shall be provided with single-station smoke alarms in accordance with Section 907.2.11. Interconnection and power sources shall be in accordance with sections 1103.8.2 and 1103.8.3, respectively.

Exception: Where smoke detectors connected to a fire alarm system have been installed as a substitute for smoke alarms.

54. Add Section 1103.11 as follows:

1103.11 Building information card.

An approved building information card shall be located in each fire command center that includes, but is not limited to, all of the following information:

1. General building information.

Includes the property name, address, the number of floors in the building above- and below- grade, use and occupancy classification (for mixed-use buildings, the different types of occupancies on each floor should be specified) and the estimated building population during the day, night, and weekends.

2. Building emergency contact information.

Includes the building’s emergency contacts, including, but not limited to the building manager; building engineer; and their respective work phone numbers, cell phone numbers, and e-mail addresses.

3. Building construction information.

Includes the type of building construction, including, but not limited to, the floors, walls, columns, and roof assembly.

4. Exit stairway information.

Includes the number of exit access stairways and exit stairways in building; each exit access stairway and exit stairway designation and floors served; the location where each exit access stairway and exit stairway discharges; interior pressurized exit stairways; exit stairways provided with emergency lighting; exit stairways that allow reentry; exit stairways providing roof access; elevator information that includes the number of elevator banks, elevator bank designation, elevator car numbers and respective floors that they serve, the location of elevator machine rooms, control rooms and control spaces; location of sky lobby; and location of freight elevator banks;

5. Building services and system information.

Building services and system information that includes the location of mechanical rooms, the location of the building management system, the location and capacity of all fuel oil tanks, the location of emergency generator(s), and the location(s) of natural gas service.

6. Fire protection system information.

Fire protection system information that includes the location of standpipes, the location of the fire pump room, the location of fire department connections, the floors protected by automatic sprinklers and location of different types of automatic sprinkler systems installed including but not limited to dry, wet, and pre-action systems.

7. Hazardous material information.

Hazardous material information that includes the location and quantities of hazardous materials.

55. Add Section 3303.11 as follows:

3303.11 Job shacks and other temporary structures.

Job shacks and other temporary structures located within or less than 20 feet from the permanent building shall:

1. Be constructed of noncombustible materials or 1-hour fire-resistive construction.

2. Not be equipped with fuel-fired heaters.

3. Be equipped with a monitored fire alarm system when located below grade.

4. Not function as offices unless protected with automatic sprinkler systems.

56. Add Section 3303.12 as follows:

3303.12 Buildings greater than 50,000 feet in area.

Buildings under construction that are defined as a high-rise or are greater than 50,000 in area shall comply with the requirements of 3303.12.1 through 3303.12.3.

3303.12.1 Job site security.

The job site shall be secured with controlled access once above-grade combustible construction has begun with off-hours guard service, motion-controlled surveillance, or both.

3303.12.2 Construction mitigations for wood frame buildings exceeding 80,000 square feet when exposures exist within 60 feet of a building under construction.

The exterior wall of the building under construction shall be covered with 5/8-inch gypsum sheathing to include windows, doors, or other openings until interior framing members have been covered with gypsum board or their finish materials.

For the purpose of measuring total square footage of wood framing, any adjacent ongoing wood-frame construction is considered to be within the project when adjacent structures are separated by less than 60 feet of open air.

Exception: A mitigation plan developed by a Washington State-licensed fire protection engineer. The mitigation plan may rely on temporary, permanent, and/or active measures.

3303.12.3 Construction mitigations for wood-frame buildings exceeding 350,000 square feet or 200,000 square feet when the building exceeds 50 feet in height.

Mitigating fire protection barriers consisting of at least one layer of 5/8-inch gypsum board or other equivalent fire resistive materials shall be installed such that the mitigating fire protection barrier(s) enclose area(s) of not more than 50,000 square feet.

For the purpose of measuring total square footage of wood framing, any adjacent ongoing wood frame construction is considered to be within the project when adjacent structures are separated by less than 60 feet of open air.

Exception: A mitigation plan developed by a Washington State-licensed fire protection engineer. The mitigation plan may rely on temporary, permanent, and/or active measures.

57. Amend Section 5001.5.2 to read as follows:

5001.5.2 Hazardous Materials Inventory Statement (HMIS).

Where required by the fire code official, an application for a permit shall include an HMIS, such as Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report or other approved statement. The HMIS shall be provided using a Redmond Fire Department-approved format and shall include the following information:

1. Product name.

2. Component.

3. Chemical Abstract Service (CAS) number.

4. Location where stored or used.

5. Container size.

6. Hazard classification.

7. Amount in storage.

8. Amount in use-closed systems.

9. Amount in use-open systems.

58. Amend Section 5003.1 to read as follows:

5003.1 Scope.

The storage, use and handling of all hazardous materials shall be in accordance with this section and shall comply with the provisions of the City of Redmond wellhead protection ordinance and critical aquifer recharge area regulations.

59. Add Section 5003.9.11 as follows:

5003.9.11 Manufacturer’s limitations.

The storage of hazardous materials shall not exceed the manufacturer’s limitations on shelf life or violate any other restrictions on use.

60. Add Section 5608.1.1 as follows:

5608.1.1 Fireworks.

Refer to Redmond Municipal Code Chapter 9.26, (Fireworks) and to RCW 70.77.120 et seq. (State fireworks law).

61. Add Section 5703.4.1, to read as follows:

5703.4.1, Secondary containment.

Secondary containment shall be provided for all new installations of storage tanks and associated piping.

62. Amend Section B102.1 to read as follows:

B102.1 Definitions

For the purpose of this appendix, certain terms are defined as follows:

FIRE FLOW: The flow rate of a water supply, measured at 20 pounds per square inch (psi) (138 kPa) residual pressure, that is available for firefighting.

FIRE-FLOW CALCULATION AREA: The building area, as defined in Chapter 2 of this Code, is used to determine the required fire flow.

63. Amend Section B104.1 to read as follows:

B104.1 General

The fire-flow calculation area shall be the area of all floor levels included within the exterior walls (or exterior walls and fire walls), exclusive of vent shafts and courts. Areas of the building not provided with surrounding walls shall be included in the fire-flow calculation area if such areas are included within the horizontal projections of the roof or floor above, except as modified in Section B104.3.

64. Amend Section B104.2 to read as follows:

B104.2 Area separation.

Portions of buildings constructed in accordance with the International Building Code (IBC) that are separated by fire walls , built per IBC Section 706 are allowed to be considered as separate fire flow calculation areas.

Additionally, Accessory Dwelling Units (ADU’s) separated from the primary structure in accordance with International Residential Code, Section 302.3, are allowed to be considered as separate fire-flow calculation areas.

65. Amend Section B105.1 to read as follows:

B105.1 One- and two-family dwellings.

The minimum fire-flow and flow duration requirements for one- and two-family dwellings shall be as specified in Tables B105.1(1) and B105.1(2).

Exception: One- and two-family homes located in areas of the City identified by the City of Redmond Water Department as having less than 1500 gpm available, may use the following formula to determine required fire flow:

Available gpm x 2.4 square feet = maximum building area

66. Amend Section B105.2 to read as follows:

B105.2 Buildings other than one- and two-family dwellings.

The minimum fire-flow and flow duration for buildings other than one- and two- family dwellings shall be as specified in Tables B105.2 and B105.2(2).

67. Amend Table B105.1(1) to read as follows:

Table B105.1(1). REQUIRED FIRE FLOW FOR ONE- AND TWO-FAMILY DWELLINGS

FIRE-FLOW CALCULATION AREA (square feet)

AUTOMATIC SPRINKLER SYSTEM (design standard)

MINIMUM FIRE FLOW (gallons per minute)

FLOW DURATION (hours)

0 – 3600

No automatic sprinkler system

1500

2

3601 and greater

No automatic sprinkler system

Value in Table B105.1(2)

Duration in Table 105.1(2) at the required flow rate

0 – 3600

NFPA 13D

1000

1

3601 and greater

NFPA 13D

50% of the value in Table B105.1(2), but not less than 1000 gpm

Duration in Table 105.1(2) at the required flow rate

68. Amend Table B105.2 to read as follows:

Table B105.2. REQUIRED FIRE FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS

AUTOMATIC SPRINKLER SYSTEM (design standard)

MINIMUM FIRE FLOW (gallons per minute)

FLOW DURATION (hours)

No automatic sprinkler system

Value in Table B105.1(2)

Duration in Table 105.1(2)

NFPA 13

50% of the value in Table B105.1(2) but not less than 3500 gpm

Duration in Table 105.1(2) at the reduced flow rate but not less than 3 hours

(Ord. 3160 § 2, 2024; Ord. 3124 § 2, 2023; Ord. 3121 § 2, 2023; Ord. 3039 § 2, 2021; Ord. 3008 § 2, 2020; Ord. 2957 § 8 (part), 2019: Ord. 2834 § 2 (part), 2016: Ord. 2693 § 2 (part), 2013: Ord. 2530 § 2 (part), 2010: Ord. 2357 § 1 (part), 2007: Ord. 2220 § 1, 2004).