A. Occupancies Prohibited. No Group H, Division 1 occupancy as defined in Section 307, International Building Code, 2018 Edition, shall be permitted.

Exception: A Group H, Division 1 occupancy may be allowed when approved by the Chief and the Building Official and authorized by a valid fire code permit.

B. Bulk Plants. Bulk plants referred to in Section 5702 of the International Fire Code, 2018 Edition, shall be prohibited throughout the City except in areas zoned Manufacturing Park (MP) or Industry (I) pursuant to the Redmond Zoning Code and shall be limited to underground storage only.

Exception: Unless prohibited by the City of Redmond wellhead protection ordinance or critical aquifer recharge area regulations.

C. Liquefied Petroleum Gas Storage. The limits referred to in Section 6104.2 of the International Fire Code, 2018 Edition, in which bulk storage of liquefied petroleum gas is restricted, are established throughout the City limits except areas zoned Manufacturing Park (MP) or Industry (I) pursuant to the Redmond Zoning Code.

D. Flammable Cryogenic Fluids. Flammable cryogenic fluids referred to in Section 5806 of the International Fire Code, 2018 Edition, shall be prohibited throughout the City except in areas zoned Manufacturing Park (MP) or Industry (I), or when approved by the Fire Code Official and the Building Official and authorized by a valid fire code permit. (Ord. 3124 § 2, 2023; Ord. 3121 § 2, 2023; Ord. 3008 § 2, 2020; Ord. 2957 § 8 (part), 2019: Ord. 2834 § 2 (part), 2016: Ord. 2693 § 2 (part), 2013: Ord. 2596 § 2 (part), 2011; Ord. 2530 § 2 (part), 2010: Ord. 2357 § 1 (part), 2007: Ord. 2220 § 1, 2004).